Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 78
PDU.Input[1].Phase[x].Statistic[5].Energy HideMeasure Energy counter since last reset. When it is reset to 0 then
at the same time the related timestamp is updated with
the current RTC value.
Wh RO
PDU.Input[1].Phase[x].Statistic[5].ModuleReset Command - RW
PDU.Input[1].Phase[x].Statistic[5].Reset.Energy HideMeasure Energy counter saved at last reset. When it is reset, at the
same time the related timer updated with PDU timer since
1st restart.
Wh RO
PDU.Input[1].Phase[x].Statistic[5].Reset.Time HideMeasure Timestamp saved at the moment where the energy counter
related to is reset.
s RO
PDU.Input[1].Phase[x].Voltage Measure Voltage Measurement. cV RO
PDU.Input[1].PowerFactor Measure Ratio of active power / apparent power provided by the
input.
Value 0 to 100 for Cos PHI = 0.00 to 1.00
m% RO
PDU.Input[1].PresentStatus.FrequencyOutOfRange AlarmL1 0: Frequency OK
1: Frequency is out of +/- 3Hz tolerance
- RO
PDU.Input[1].ReactivePower Measure Reactive Power Measurement.
It is the accumulation of 1 or 3 phase measures.
dVA
R
RO
PDU.Input[1].Statistic[3].ActivePower Measure Power peak consumption since last reset.
As it is reset to 0, the related timestamp is updated with
the current RTC value.
When a value higher than the stored value is detected, the
stored valued is overwritten.
dW RO
PDU.Input[1].Statistic[3].ModuleReset Command Command to Reset the stat. This command puts 0 in the
max and saves the current value of Timer into the data
…Timer and into ...Reset.Timer.
- RW
PDU.Input[1].Statistic[3].Reset.Time Measure Timestamp saved at the moment when the statistic is
reset.
s RO
PDU.Input[1].Statistic[3].Time Measure Timestamp saved at the moment when the statistic is
reset.
s RO
PDU.Input[1].Statistic[4].Energy Measure Energy counter since last reset. As it is reset to 0, the
related timestamp is updated with the current RTC value.
It combines the energy consumed on 1 or 3 phases.
Wh RO
PDU.Input[1].Statistic[4].ModuleReset Command Command to Reset the stat. This command does not put 0
in the counter, but it saves the current value of Energy
timer into the data ...Reset.Energy.
s RW
PDU.Input[1].Statistic[4].Reset.Energy Measure Energy saved at the instant the user resets the stat. Wh RO
PDU.Input[1].Statistic[4].Reset.Time Measure Timestamp saved at the instant the user resets the stat. s RO
PDU.Input[1].Statistic[5].Energy Measure Energy counter since last reset. When it is reset to 0 then
at the same time the related timestamp is updated with
the current RTC value.
It cumulates the energy consumed on 1 or 3 phases.
Wh RO
PDU.Input[1].Statistic[5].ModuleReset Command Command to Reset the stat, this command does not put 0
in the counter but saves the current value of Energy timer
into the data ...Reset.Energy.
s RW
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access