Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 79
PDU.Input[1].Statistic[5].Reset.Energy Measure Energy saved at the instant the user resets the stat. Wh RO
PDU.Input[1].Statistic[5].Reset.Time Measure Timestamp saved at the instant the user resets the stat. s RO
PDU.Input[1].Type Constant List types of PDU Input plugs. - RO
PDU.Input[2].ActivePower Measure Active Power Measurement.
It's the cumul of 1 or 3 phase measures.
dW RO
PDU.Input[2].ApparentPower Measure Apparent Power Measurement.
It's the cumul of 1 or 3 phase measures.
dVA RO
PDU.Input[2].ChangedStatus.FrequencyOutOfRange Timestamp s RO
PDU.Input[2].Frequency Measure Frequency Measurement. dHz RO
PDU.Input[2].Mode Constant Wiring Mode
0: Wye Measuring
1: Delta Measuring
2 : Wye Current and Delta Measuring
- RO
PDU.Input[2].Phase.Count Constant Number of phase managed by the Input module. - RO
PDU.Input[2].Phase[x].ActivePower Measure Active Power Measurement. dW RO
PDU.Input[2].Phase[x].ApparentPower HideMeasure Apparent Power Measurement. dVA RO
PDU.Input[2].Phase[x].ChangedStatus.OverCurrent Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
PDU.Input[2].Phase[x].ChangedStatus.OverVoltage Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
PDU.Input[2].Phase[x].Current Measure Current Measurement. mA RO
PDU.Input[2].Phase[x].OverCurrent[1].Threshold Parameter mA RW
PDU.Input[2].Phase[x].OverCurrent[3].Threshold Parameter mA RW
PDU.Input[2].Phase[x].OverCurrent[4].Threshold Parameter mA RW
PDU.Input[2].Phase[x].OverVoltage[1].Threshold Parameter cV RW
PDU.Input[2].Phase[x].OverVoltage[2].Threshold Parameter cV RW
PDU.Input[2].Phase[x].OverVoltage[3].Threshold Parameter cV RW
PDU.Input[2].Phase[x].OverVoltage[4].Threshold Parameter cV RW
PDU.Input[2].Phase[x].PeakFactor Measure Crest factor of the current provided by the phase. m% RO
PDU.Input[2].Phase[x].PercentLoad Measure Percent load consumed on the phase. It is the ratio :
current consumed / the nominal current of the PDU.
% RO
PDU.Input[2].Phase[x].PhaseID Constant Phase ID identifier depending of the wiring :
1 : Line 1 to Neutral
2 : Line 2 to Neutral
3 : Line 3 to Neutral
- RO
PDU.Input[2].Phase[x].PowerFactor HideMeasure Ratio of active power / apparent power provided by the
phase.
Value 0 to 100 for Cos PHI = 0.00 to 1.00
m% RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access