Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 80
PDU.Input[2].Phase[x].PresentStatus.OverCurrent AlarmL1 0 : No threshold trigged
1 : Warning low threshold trigged
2 : Critical low threshold trigged
3 : Warning high threshold trigged
4 : Critical high threshold trigged
- RO
PDU.Input[2].Phase[x].PresentStatus.OverVoltage AlarmL1 0 : No threshold trigged
1 : Warning low threshold trigged
2 : Critical low threshold trigged
3 : Warning high threshold trigged
4 : Critical high threshold trigged
- RO
PDU.Input[2].Phase[x].ReactivePower HideMeasure Reactive Power Measurement. dVA
R
RO
PDU.Input[2].Phase[x].Statistic[5].Energy HideMeasure Energy counter since ePDU start. Wh RO
PDU.Input[2].Phase[x].Statistic[5].ModuleReset Command Command to Reset the stat, this command does not put 0
in the counter but saves the current value of Energy timer
into the data ...Reset.Energy.
- RW
PDU.Input[2].Phase[x].Statistic[5].Reset.Energy HideMeasure Energy saved at the instant the user resets the stat. Wh RO
PDU.Input[2].Phase[x].Statistic[5].Reset.Time HideMeasure Timestamp saved at the instant the user resets the stat. s RO
PDU.Input[2].Phase[x].Voltage Measure Voltage Measurement. cV RO
PDU.Input[2].PowerFactor Measure Ratio of active power / apparent power provided by the
input.
Value 0 to 100 for Cos PHI = 0.00 to 1.00
m% RO
PDU.Input[2].PresentStatus.FrequencyOutOfRange AlarmL1 0 : Frequency OK
1 : Frequency is out of +/- 3Hz tolerance
- RO
PDU.Input[2].ReactivePower Measure Reactive Power Measurement.
It's the cumul of 1 or 3 phase measures.
dVA
R
RO
PDU.Input[2].Statistic[3].ActivePower Measure Power peak consumption since last reset.
When it is reset to 0 then at the same time the related
timestamp is updated with the current RTC value.
When it is detected higher than the value stored, so it
overwrites it.
dW RO
PDU.Input[2].Statistic[3].ModuleReset Command Command to Reset the stat, this command put 0 in the max
and saves the current value of Timer into the data …Timer
and into ...Reset.Timer.
- RW
PDU.Input[2].Statistic[3].Reset.Time Measure Timestamp saved at the moment where the statistic is
reset.
s RO
PDU.Input[2].Statistic[3].Time Measure Timestamp saved at the moment where the statistic is
reset.
s RO
PDU.Input[2].Statistic[5].Energy Measure Energy counter since ePDU start.
It cumulates the energy consumed on 1 or 3 phases.
Wh RO
Table 8. ePDU CLI Objects (Continued)
XML Object Name Type Description Unit Access