8 What you need to know about SmartWire-DT
8.5 SWD device parameters
SmartWire-DT Gateway EU5C-SWD-EIP-MODTCP 08/17 MN120003Z EN www.eaton.com 93
8.5.2 Device parameters of SWD modules
Table 27: Device parameters of SWD modules
Device parameter
adjustable on SWD
module
Value Reaction SmartWire-DT
Required module 1 Required SWD module
1=Setpoint value
The SWD module must be present when the system
starts and during operation.
A missing SWD module causes following:
PRSNT diagnostic bit to be set to "0"
DIAG diagnostic bit to be set to "1"
The SWD line will not start running or will be
stopped, as the case may be.
Note:
This device parameter will only take effect if the coordi-
nator's ""All devices are optional" device parameter is
disabled, i.e., if it has a value of "0".
0 The SWD line will keep running even if the SWD module
is missing or defective.
Can be replaced with
universal module
0 0=Setpoint value
The SWD module can not be replaced by a universal
module M22-SWD-NOP(C).
1 The SWD module can be replaced by a universal module
M22-SWD-NOP(C).