Loading...
Responding to System Events
12-3
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
ALARMS
Indication
Log*RelayPhoneHorn
Message
Configuration Error 1 No 1 HA Service Required
Configuration Error OK Off No 1 HA Condition Cleared
External Comm Failure 1 No 1 HA Service Required
External Comm Failure OK Off No 1 HA Condition Cleared
Internal Comm Failure 1 No 1 HA Service Required
Internal Comm Failure OK Off No 1 HA Condition Cleared
Invalid Board ID 1 No 1 HA Service Required
Invalid Board ID OK Off No 1 HA Condition Cleared
Inverter L1 Current Limit 1 No 1 HA Service Required
Inverter L2 Current Limit 1 No 1 HA Service Required
Inverter L3 Current Limit 1 No 1 HA Service Required
Inverter Output Failure 1 1 1 HA Service Required
Inverter Output Failure OK Off No 1 HA Condition Cleared
Inverter Overtemperature 1 No 1 HA Service Required
Inverter Overtemperature OK Off No 1 HA Condition Cleared
Inverter Overtemperature Trip 1 No 1 HA Service Required
Inverter Overtemperature Trip OK Off No 1 HA Condition Cleared
L1 Overload 1 No 1 HA User Action Required
L1 Overload OK Off No 1 HA Condition Cleared
L1 Overload (Extreme Level) 1 No 1 HA User Action Required
L1 Overload (Extreme Level) OK Off No 1 HA Condition Cleared
L1 Overload (High Level) 1 No 1 HA User Action Required
L1 Overload (High Level) OK Off No 1 HA Condition Cleared
L2 Overload 1 No 1 HA User Action Required
L2 Overload OK Off No 1 HA Condition Cleared
L2 Overload (Extreme Level) 1 No 1 HA User Action Required
L2 Overload (Extreme Level) OK Off No 1 HA Condition Cleared
L2 Overload (High Level) 1 No 1 HA User Action Required
L2 Overload (High Level) OK Off No 1 HA Condition Cleared
L3 Overload 1 No 1 HA User Action Required
L3 Overload OK Off No 1 HA Condition Cleared
L3 Overload (Extreme Level) 1 No 1 HA User Action Required
L3 Overload (Extreme Level) OK Off No 1 HA Condition Cleared
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and