Loading...
164201554---2 1 of 2
PHYSICAL FEATURES AND REQUIREMENTS
081505C
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
Installation Information
A-3
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
1. The UPS equipment operating environment must meet the weight requirements shown in
Table A and the size requirements shown on Drawing 164201554---9.
2. The UPS cabinet is palleted separately for shipping.
3. Donottiltcabinetsmorethan10˚ during handling.
4. Dimensions are in millimeters (inches).
5. Thecabinetcanbeinstalledinline-up-and-match or standalone configurations.
Table A. UPS Cabinet Weight
Model
Voltage
Weight
kg (lb)
Input Output Shipping Installed Point Loading
Powerware 9390---120/100 208V/220V 208V/220V 531 (1170) 504 (1110) 6 at 84 (185)
Powerware 9390---120/100 480V 480V 467 (1030) 440 (970) 6 at 73 (162)
Powerware 9390---120/120 208V/220V 208V/220V 531 (1170) 504 (1110) 6 at 84 (185)
Powerware 9390---120/120 480V 480V 467 (1030) 440 (970) 6 at 73 (162)
Powerware 9390---160/100 208V/220V 208V/220V 581 (1280) 553 (1220) 6 at 92 (204)
Powerware 9390---160/100 480V 480V 517 (1140) 490 (1080) 6 at 82 (180)
Powerware 9390---160/120 208V/220V 208V/220V 581 (1280) 553 (1220) 6 at 92 (204)
Powerware 9390---160/120 480V 480V 517 (1140) 490 (1080) 6 at 82 (180)
Powerware 9390---160/160 208V/220V 208V/220V 581 (1280) 553 (1220) 6 at 92 (204)
Powerware 9390---160/160 480V 480V 517 (1140) 490 (1080) 6 at 82 (180)
6. The clearances required around the UPS cabinet are shown in Table B.
Table B. U PS Cabinet Clearances
From Top of Cabinet Minimum clearance over the UPS cabinet is
457.2 mm (18 in.) for ventilation
From Front of Cabinet 914.4 mm (36 inches) working space
From Back of Cabinet None required
From Right Side of Cabinet None required
From Left Side of Cabinet None required