SC200 Handbook
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Notes:
1 The parameters available are: Bus Voltage, Rectifier Current, Load Current, Battery Current,
Battery Temperature, Load Power, System Power, Analog Input, or Ah Discharged.
2 If Analog Input is selected as a display parameter, then also select a value for Value 1/2/3
Index. This value is the number of the AI from the Analog Inputs table. To view the table in
DCTools/Web go to: Analog Inputs.
Display Time-out
If there is no keypad activity for 60 seconds the display will go back to the main screen.
Alarm Indicators
Visual indicators
Critical/Major Alarm LED (red)
The system value cannot be displayed because of a failed, disconnected or
unconfigured sensor.
Audible indicator
One beep – indicates an invalid key press
Three beeps every 2 seconds – refer to the alert message on the display
One beep every 2 seconds – Minor alarm is active
Continuous sound – Critical/Major alarm is active
Critical/Major alarms always override Minor alarms.
► To stop the audible indicator
Press any key
The audible indicator will restart at the next active alarm or alert message.
► To enable/disable the audible alarm indicator
Either:
Use the keypad to go to: Alarms > Alarm Settings (tab) > Audible Alarms > Edit.
Or:
In DCTools/Web go to: Alarms > Alarm Configuration.
When Disabled, the audible indicator will still indicate an invalid key press.