SC200 Handbook
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Rectifiers
The SC200 registers all rectifier modules as they are inserted into the dc power system.
Information
The following information is available about rectifiers.
Registered - communicating with the SC200.
Un-registered - there is a rectifier compatibility or
communications problem.
SC200: Rectifiers > Enter
(Use Left and Right keys to
scroll to other rectifiers)
DCTools/Web: Rectifiers
The time the rectifier has been operating since it was
registered.
The ac voltage measured by the rectifier (single-phase
rectifiers only).
The ac phase voltages measured by the rectifier (three-
phase rectifiers only).
Rectifier's dc output voltage.
Rectifier's output current.
The measured rectifier heatsink temperature.
Rectifier's maximum output power (factory set).
Rectifier output power as a percentage of Max. Power
Limit.
The maximum current limit value of the rectifier.
Adjust Rectifier Current Limit to set a lower
operating current limit.
The minimum Over Voltage Shut Down set point that
the rectifier accepts.
The maximum Over Voltage Shut Down set point that
the rectifier accepts.
Information about rectifier alarms.
Rectifier manufacturer's model number.
SC200: Rectifiers > Enter
(Use Left and Right keys to
scroll to other rectifiers)
Version of rectifier embedded software.