System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Common Rectifier Configuration
The following parameters (common to all rectifiers) can be configured.
Rectifier (DC)
Current Limit
The output current limit of the rectifier. If set to zero,
then the output current limit is maximum.
SC200: Rectifiers > Rect.
Settings
DCTools/Web: Rectifiers
AC Rectifier
Current Limit
The input current limit of the rectifier. If set to zero,
then the input current limit is maximum.
Current Share ensures that the total output power of
the power system is evenly shared between all
rectifiers.
Set to Enabled unless there is a specific reason to
disable.
Over Voltage Shut Down. A rectifier will shut down if
its output voltage exceeds this value.
Recommended value is 59.2V for 48V nominal
systems, 28.6V for 24V nominal systems.
The ramp-up slope of the rectifier, as a percentage of
the rectifier rated current.
The delay from ac turn-on before the rectifier output
turns on.
See Voltage Control on page 22 for details of the rectifier's output voltage control.
Identify a Rectifier
The rectifier's registration number does not correspond to a physical position in the dc power
system.
► To identify a rectifier
Either:
On SC200 keypad go to: Rectifiers > Rectifier number. Press Enter.
The rectifier details screen appears. Use to scroll to other rectifiers.
All LEDs on the selected rectifier will flash for 60 seconds, or press Esc to stop.
Or:
In DCTools/Web go to: Configuration > RXP > RXP Devices.
DCTools: select Identify Device or Web: click on Start Identifying.
All LEDs on the selected rectifier will flash for 60 seconds.
Rectifier serial numbers are printed on a label on the front of each rectifier.