EasyManua.ls Logo

Eaton SC200 - Dctools or Powermanagerii Communications Setup (if Required)

Eaton SC200
139 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
83
SC200 Setup
The network administrator must assign a unique IP address to each SC200 to be connected to the
TCP/IP network.
To configure an SC200 for Ethernet communications from the keypad
Go to Settings > Setup
Enter the IP Address, Subnet Mask and Gateway Address assigned by the network
administrator.
If required, set HTTP Access to Enabled for web browser access, or set HTTPS Access to
Enabled for secure web access.
To configure an SC200 for Ethernet communications using DCTools
Connect using USB (see details on page 13).
In DCTools go to Configuration > Communications.
Under Ethernet, type the IP Address, Subnet Mask and Gateway Address assigned by the
network administrator.
If required, under HTTP (Web), set HTTP Access to Enabled for web browser access, or set
HTTPS Access to Enabled for secure web access.
DCTools or PowerManagerII Communications Setup (if required)
To connect to the SC200 with DCTools or PowerManagerII:
1 Install DCTools/PowerManagerII on the PC/laptop.
2 Double-click the DCTools/PowerManagerII icon to open the connection manager.
3 Go to Connection > New to open a new connection dialog box.
4 Enter:
Connection Name:
<as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Ethernet
S3P Address:
0 (0 = Broadcast, 1-65279 = individual address)
Server IP Address:
Allocated by network administrator
Server Port:
Allocated by network administrator
Telnet
Cleared
5 Press OK. DCTools/PowerManagerII will now connect to the SC200.
6 See System Operation on page 21 for details of the SC200 control and monitoring functions
available via DCTools.
For help using DCTools press F1.
7 If required, access to the SC200 via DCTools or PowerManagerII can be password
controlled. See Write Access Password on page 95.

Table of Contents