Active Alarm Indications
All alarms have a configured Severity:
Critical Major Minor Warning Control
The Severity determines how an active alarm is indicated:
SC200 Major alarm LED will turn on.
SC200 Minor alarm LED will turn on.
If the SC200 audible indicator is enabled, it will
sound until a key is pressed.
The alarm name and severity icon will be
displayed on the SC200 main screen.
The Event Log will record the alarm activation.
If configured, an Email message will be sent to one
or more Email addresses.
If configured, an SMS text message will be sent to
one or more cell phones.
If configured, PowerManagerII control and
monitoring software will be notified by modem
callback. PowerManagerII can initiate various
actions when it receives an alarm notification.
Refer to the
PowerManagerII online
Help.
In DCTools/Web (if connected), the alarm name
and severity icon will be displayed in the Alarms
list on the System page.
See DCTools screen on
page 13, Web screen on
page 84.
If configured, an SNMP Trap will be sent to a
network management system (NMS).
If configured, a note will be displayed on the
SC200 and included in the SNMP trap (if used).
Refer to the alarm's
configuration details.
If configured, one or two digital outputs (relays)
will be operated.
Refer to the alarm's
configuration details.
► To view a list of active alarms
Use the SC200 keypad to go to: Alarms.
Or, in DCTools/Web go to System.