Communications
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Communication via Email
The SC200 system controller can be configured to send Email alarm messages when an alarm
occurs.
► To set up Email communications:
1 Set up Ethernet communications and connect the SC200 to the IP network. See Ethernet
Communications on page 82.
2 In DCTools/Web go to Configuration > Communications > Email Notifications.
3 Enable Email Notifications.
4 Set the following parameters:
SMTP Server IP Address
and Port:
The details of the mail server that will be used to send
the Emails.
If not blank, any delivery failure notifications will be
sent to this address.
An Email subject prefix that will be added to each
Email's subject to allow automatic processing of the
Email.
5 For each Email recipient (up to 6), set the following parameters:
The recipient's Email address.
The severity of alarms that are to be reported to this
recipient.
Select Warnings And Above to send an Email when
an alarm with a severity of Warning or above
changes state.
Select Minor And Above to send an Email when an
alarm with a severity of Minor or above changes
state.
Select Major And Above to send an Email when an
alarm with a severity of Major or above changes
state.
Select None to send no Emails.
Select Critical Only to send an Email when an
alarm with a severity of Critical changes state.
The alarm Email will be delayed by this length of
time. During this delay, the SC200 will collate all the
events that occur into a single Email.
Test Emails can be sent to test the Email Communication setup.
► To send a test Email:
1 In DCTools/Web go to Configuration > Communications > Email Notifications.
2 Click the Send Test Email button on the row of the Email address to be tested.