System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
► To configure a Smart Alarm Disconnect
1 In DCTools/Web go to: Alarms > Smart Alarms. Configure a Smart Alarm as described on
page 50.
2 Note the SA Number (first column of the Smart Alarm States table).
3 Go to: Control Processes > LVD.
4 For the required LVD control channel:
Set Smart Alarm Index to the SA Number (first column of the Smart Alarm States table).
Set Smart Alarm based Disconnect to Enabled.
The LVD control channel will disconnect its contactor(s) if the Smart Alarm becomes active.
Except, if Chained to Previous is enabled then the preceding LVD control channel must be
disconnected first.
Alarms
An SC200 supplied with a standard configuration file (see details on page 18) has a standard set
of alarms configured and enabled. This will be sufficient for standard dc power system
operation.
For specific alarm arrangements all SC200 alarms can be individually enabled or disabled and
are configurable.
Types of Alarms
The SC200 provides five types of alarms:
Generated by the operating values of dc power
system (voltages, currents, temperatures, and
so on) and the operation of power system
modules (rectifiers, circuit breakers, fuses, and
so on). The SC200 system alarms are listed in
Alarm Descriptions on page 109.
Analog Input
(AI) High alarms
Activated when the input value of an AI is
above the alarm threshold.
Analog Input
(AI) Low alarms
Activated when the input value of an AI is
below the alarm threshold.
Digital Input (DI)
alarms
Activated when a DI is in its active state.
Software simulation of logic gates to allow the
logical combination of other alarms, time
schedules and/or system values.