SC200 Handbook
50
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Sources
The inputs to Smart Alarms are called Sources.
Sources can be any combination of:
Alarm Sources (up to 64):
System Alarms, Analog Input High alarms, Analog Input Low alarms, Digital Input
alarms, Other Smart Alarms
Alarm Sources can either use the alarm’s recognition period,or be triggered immediately.
Alarm Sources can also be triggered either when the source alarm becomes active or when it
becomes inactive.
Time Schedules (up to 20)
Time schedules can repeat for a fixed number of times, or indefinitely.
System Values (up to 20):
Bus Voltage, Rectifier Current, Load Current, Battery Current, Battery Temperature, Load
Power, System Power, Ah Discharged, Number Of Rectifiers Failed, Number Of Rectifiers
Comms Lost, AC Voltage, Battery Time Remaining, Alternative Source Current, Highest
Rectifier Heatsink Temperature, Fuel Level, Generator Backup Time, Fuel Remaining Time.
System Value Sources are active either when the system value is above or below a defined
threshold value.
Configuration
Information
The following information is available about Smart Alarms and Sources.
Parameter
Description
Where to find:
Smart Alarm State
The present state of the Smart Alarm. If Enabled
and active, this will be the alarm's Severity. If
Disabled, or Enabled but inactive, the state is
shown as "-".
DCTools/Web: Alarms >
Smart Alarms > Smart
Alarm States
Source Triggered
The present state of the source:
= Enabled and active
"-" = Disabled, or Enabled but inactive.
= There is an invalid dependency, or the
source Index is invalid.
= The source is part of a circular dependency.
DCTools/Web: Alarms >
Smart Alarms > Sources
Next Activation
The date and time this schedule will next
activate.
DCTools/Web: Alarms >
Smart Alarms > Schedule
Sources
Schedule End
The date and time this schedule will activate for
the last time.