SC200 Handbook
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Data Log
The Data Log records several system parameters (AC Voltage, Bus Voltage, Load Current,
Rectifier Current, Battery Current, Battery Temperature) at specified intervals. The rate of
recording increases (interval is reduced) when the bus voltage differs from the float voltage by
more than a specified value.
Data log entries are also written whenever a system event occurs (as for the Event Log).
► To view and save the Data Log
To view the log entries, either:
In DCTools go to: Controller Log > Event Log , or
In Web go to Logs > Log Management and click Data Log (CSV): Download to view the log
entries in a new browser window.
Wait for the log entries to download from the SC200.
To save the log to a file, either:
In DCTools click on Save to File ... , or
In Web go to File > Save As...
Type a file name, select a file type, and browse to a location to save the file.
► To configure the Data Log
Either:
In DCTools go to: Controller Log > Configuration, or
In Web go to Logs > Data Log Config.
The following parameters must be configured.
The time between each data log record when the Bus
Voltage differs from the Float Voltage by less than the
Off-Normal Offset Voltage.
Web: Logs > Data Log
Config
DCTools: Controller Log >
Configuration > Data Log
Config
The time between each log record when the Bus
Voltage differs from the Float Voltage by more than the
Data Log Off-Normal Offset Voltage.
Off-Normal Offset
Voltage
The Off Normal Log Interval will apply when bus
voltage is outside the range: Float Voltage ± Off-
Normal Offset Voltage. Off-normal condition
transitions are recognized within 10 seconds.
Maximum Number
of Log Entries
Memory will be allocated for at least this number of
Data Log entries (up to 10,000). When the memory is
full the oldest record will be over-written.
► To clear the Data Log
In Web go to Logs > Log Management or in DCTools go to Controller Log > Configuration >
Log Management.
Click Clear Logs.
This will also clear the Event Log.
PC Log
The PC Log allows a continuous streaming of system data (Bus Voltage, Load Current, Battery
Current, Battery Temperature, Rectifier Current, Load Power, System Power) from the SC200
directly into a specified file.