System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
► To configure and activate the PC Log
1 In DCTools go to PC Log.
2 At File Name, click on the button to type a file name, select a file type, and browse to a
location to save the file.
3 Select the required interval between log entries (from 5s to 60 minutes).
4 Click on Start to begin the log.
5 Click on Stop to end the log.
PC Log is only available through DCTools, not through the SC200 web server.