3. Installation
3.1 Prerequisites for the location of use
3. Installation
3.1 Prerequisites for the location of use
The XV300 must be used exclusively in locations for which the HMI panel has been
approved/certified.
A 24 VDC supply voltage must be ensured as per the specifications.
See also
Label on the "Nameplate", page 23
The specifications in the appendix → Section "Technical data", page 70
3.1.1 Installation position
The following must be taken into account when selecting the installation position:
l If you will be using the HMI panel in a hazardous (explosive) location, make sure it is
not exposed to any dangerous impacts or other types of dangerous mechanical
shock.
l The controls and connectors on the XV device's service side must remain access-
ible even after the device has been installed.
The SD card slot is located on the side of the XV300.
Make sure to take the space required to remove the SD card into
account.
Figure 11: Space required to remove the SD card
3.1.1.1 Temperatures
Make sure that the HMI panel does not overheat.
Do not expose the HMI panel to direct sunlight or other sources of heat.
The minimum clearance to components emitting heat, such as transformers under
heavy loads, is 15 cm.
CAUTION
UVLIGHT
PlasticswillbecomebrittlewhenexposedtoUVlight.Thisartificialaging
willreducetheXV300unit'slifespan.ProtecttheXV300unitfromdirectsun-
lightandothersourcesofUVradiation.
XV30012/15 MN048017 ENwww.eaton.eu
31