5. External connections
5.6 CAN1 interface for the CANopen protocol, J1939 protocol, etc.
The maximal baud rate depends on the cable length
Possible baud rates
With a max. cable length
of
25 m
1000 kBit/s
50 m
800 kBit/s
100 m
500 kBit/s
M 250
250 kBit/s
500 m
125 kbit/s
500 m
100 kBit/s (can be set through soft-
ware)
1000 m
50 kBit/s
2500 m
20 kBit/s
5000 m
10 kBit/s
Whenpreparingconnections,ensurethatthecableshieldhasalow
impedanceconnectionwiththeconnectorhousing.
5.6.0.2 CAN-Bus-topology
l A bus segment can interconnect up to 32 slaves.
l Several bus segments can be connected using repeaters (bi-directional amplifiers).
The use of repeaters enables the maximum cable length to be
increased.
Repeaterscanalsobeusedforgalvanicisolation.Formoredetails,
pleaseconsultthedocumentationforrepeatersprovidedbyman-
ufacturer.
MakesuretofollowtherecommendationsprovidedbyCiA(CANinAuto-
mation)athttp://www.can-cia.org.
A bus segment must be provided with cable termination (120 Ohm) at both ends.
These terminals must be connected in the plug directly between pin 2 and 7.
Thebussegmentmustbeterminatedatbothends.
Nomorethantwoterminationsmustbeprovidedforeachbussegment.
Operationwithoutcorrectcableterminationcancausetransfererrors.
Figure 30: CAN bus segment with four nodes
56
XV30012/15 MN048017 ENwww.eaton.eu