EasyManua.ls Logo

Eaton XV300 Series - SWD Power Supply Voltages

Eaton XV300 Series
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. External connections
5.8 XV300 Touch Panel as a SmartWire-D coordinator
Conditions for Underwriters Laboratories Inc. (UL) certification
The SmartWire-DT® master interface's U
Aux
supply voltage must be externally pro-
tected against overcurrent and short-circuits with the following:
l Miniature circuit-breaker 24 V
DC
, rated operational current 2 A, trip type Z
l or a 2 A fuse.
5.8.1.1 SWD power supply voltages
The following power supplies are required for a SmartWire-DT® network:
l POW supply voltage:
The device supply voltage for the electronics in the downstream SmartWire-DT®
modules (15 V DC) is generated using the 24 V DC supply voltage applied at the POW
terminal.
l AUX supply voltage:
If there are any contactors or motor starters in the SmartWire-DT® topology, a 24 V
DC AUX voltage must be additionally supplied as a control voltage for the contactor
coils.
POW/AUX power supply interface
The Plug connector WAGO 734-104 plug connector is included with the device.
Electrical connection
Figure 33: WAGO plug connector (view from wiring side)
Plug connector PIN Signal Description
4-Pole
1
+24 V DC POW
Supply voltage U
POW
+24 V DC
2
0 V POW
Supply voltage U
POW
0V
3
+24 V DC AUX
Supply voltage U
AUX
+24VDC
4
0 V AUX
Supply voltage U
AUX
+0 V
Table20:PinassignmentWAGOplugconnector
Observe the following when assembling and terminating the wiring for the plug con-
nector:
60
XV30012/15 MN048017 ENwww.eaton.eu