3. Installation
3.1 Prerequisites for the location of use
3.1.1.3 Criteria for the installation position
The XV300 are intended to be flush mounted in control cabinets, control panels, or con-
trol consoles.
l XV300 units can be installed in landscape or portrait mode.
If you are using your XV300 unit with an SD card, do not install it with the SD slot
facing downwards, as the SD card may fall out otherwise.
l
If no forced ventilation is being used, the device must not be mounted at an angle
of more than ±α ≦ 45° relative to its fully vertical position.
l The enclosure material must be thick enough
For front mounting: 2 mm (0.08") d 5 mm (0.2"),
For rear (panel) mounting: d = 1.5 mm (0.059") ± 0.1mm (0.004")
Flatness 0.5 mm (0.02") at the mounting cutout with Rz ≦ 120; IP 65 DIN
ISO2768-2 (K)
l Recommended mounting cutout
For front mounting:
XV-303-70-..:e = 183mm (7.20") ± 1mm (0.04"), f=122mm (4.80") ± 1mm (0.04")
XV-303-10-..: e = 255.5mm (10.06") ± 1mm (0.04"), f = 160.5mm (6.32") ± 1mm (0.04"),
For rear (panel) mounting:
XV-313-70-..: e = 182.7mm (7.193") ± 0.1mm (0.004"), f = 126.8mm (4.992") ± 0.1mm
(0.004")
XV-313-10-..: e = 255.7mm (10.07") ± 0.1mm (0.004"), f = 165.8mm (6.528") ± 0.1mm
(0.004")
Figure 14: Mounting position
XV30012/15 MN048017 ENwww.eaton.eu