ABTAUUHR
POS: XXXXX
Input Default
Sicherheitsz.
XXX m
Safe defrost time for the maximum permitted duration of the defrost (only
applicable for the internal defrost)
man. Abtauung
XXX
State (OFF/ON) for an additional manual defrost *) - only displayed if parameter
Abtauuhr = INT
, , (OFF/ON)
OFF
Abt.Uhr Z2 Separate defrost timer for zone 2 Menu 3-2-a
Abtau 1 xxxxx hh:
mm
Start time for the defrost with internal defrost; day of the week, time; - only
displayed if parameter Abtauuhr = INT
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
05:00
Abtau 2 xxxxx hh:
mm
Start time for the defrost with internal defrost; day of the week, time; - only
displayed if parameter Abtauuhr = INT
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
7:00
AM
Abtau 3 xxxxx hh:
mm
Start time for the defrost with internal defrost; day of the week, time; - only
displayed if parameter Abtauuhr = INT
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
1:00
PM
...
Abtau 14 xxxxx
hh:mm
*) The parameter is automatically set to ON after the first start for the duration of the safe defrost
time.
Menu 3-3 Sollw. Umschaltung
UMSCHALTNG
POS: XXXXX
Input Default
Status XXX Status (OFF/ON) of the toggle setpoint for the alternative setpoint set
(toggle setpoint set)
Sollumschaltg. XXX Type of the toggle setpoint using:-
EXT = external via digital input D21/22-
INT = internal clock-
CAN = CAN bus - "--"= deactivated toggle setpoint
, , (EXT, INT, CAN, --)
EXT
Um EIN TT-TT hh:
mm
Start time of the changeover to the alternative setpoint set;
weekday from-to TT-TT, time hh:mm; only displayed for active internal
toggle setpoint (menu 3-3)
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
21:00
Um AUS TT-TT hh:
mm
End time of the changeover to the alternative setpoint set;
weekday from-to TT-TT, time hh:mm; only displayed for active internal
toggle setpoint (menu 3-3)
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
5:00
AM
Um EIN TT-TT hh:
mm
Start time of the changeover to the alternative setpoint set;
weekday from-to TT-TT, time hh:mm; only displayed for active internal
toggle setpoint (menu 3-3)
, , (Mon-Sun etc.) or
numbers (hh:mm)
Sun
05:00
Um AUS TT-TT hh:
mm
End time of the changeover to the alternative setpoint set;
weekday from-to TT-TT, time hh:mm; only displayed for active internal
toggle setpoint (menu 3-3)
, , (Mon-Sun etc.) or
numbers (hh:mm)
Sun
9:00
PM
... A total of 14 different ON, OFF toggle times can be recorded.
A toggle time is only observed if an of switch-on and switch-
associated pair
off time is parametrised.