KGL Operating Manual – UA 412 S 2019-01-14 /94 122
*) The status abcdef contains the following states of the refrigeration point. If a state is not active, a "-
" is entered here. Example: Zone 1: abcdefx °C
Single-zone operation or BT 300 operator interface
a B = Operation
b K = Cooling
c K = Cooling
d A = Defrost
e T = door (only for room controller)
f W = Warning (alarm)
9.1.7 Menu 6 Configuration
KONFIGURAT POS: XXXXX
1 Refrigeration point Continue to menu 6-1
2 Controller Continue to menu 6-2
3 Cooling Continue to menu 6-3
4 Language Continue to menu 6-4
5 Alarm Priorities Continue to menu 6-5
6 Emergency power operation Continue to menu 6-6
Menu 6-1 - Refrigeration point
KÜHLSTELLE POS:
XXXXX
Input Default
Refr. Pt. Name: Only text
xxxxxxxxxxxxxxx Free text that designated the refrigeration point (see note after the table) Case
controller
Position: XXXXX Free text that is displayed in the menu after position (POS) (see note after the
table)
UA400
Priority: XX Priority of the alarms for refrigeration point failure or setting of the global controller
priority (menu 6-5)
, , or numbers
(0..99)
1
Fühleranzahl XX Display of the connected temperature sensors
After input of , a sensor scan is performed, during which the number of sensors
is determined again.
The priority for older versions of the store computer (<V5.0) may only be allocated in the range 0..2;
.see chapter Alarm signalling and monitoring, page 114
A meaningful name should be entered which provides details about the position of the sensor, e.g.
Cheese Counter 2 and KT2. The input is made using the menus of the system centre / store
computer / operator terminal. Direct input using the menus of the case controller shown in the
operator terminal is not possible. It is also not possible to make the entry using the BT 300 operator
interface.