KGL Operating Manual – UA 412 S 2019-01-14 /111 122
ALARMPRIOSPOS: XXXXX Input Default
Sensor fault Temperature sensor failed -, 0..
99
0
No Defrost No defrost within the alarm delay time
Priority is applicable for the message
No Defrost
-, 0..
99
0
Timer-Term. Defrost Defrost ended by safe defrost time -, 0..
99
0
Power failure Start-up after power failure -, 0..
99
0
First start Commissioning of the controller (basic
settings loaded!)
-, 0..
99
0
Manual shutdown Manual control switch input D31/D32
on OFF
-, 0..
99
0
Hardware fault The internal hardware has a fault
Priority is applicable for the messages
EEPROM fault, RTC fault, Flash fault
-, 0..
99
1
Sollwertverst. Message is generated during setpoint
adjustment
0..99 0
Refrig.Pt.Dis. Cooling interrupted by VS via CAN bus -, 0..
99
0
Battery voltage Low battery voltage -, 0..
99
0
Safety chain Safety chain -, 0..
99
1
Verdichter Endt. Compressor end temperature -, 0..
99
0
Menu 6-6 - Emergency power operation
NOTNETZPOS: XXXXX Input Default
Fkt. Kühl. AUS xxx Cooling functionality switched off during emergency power operation? (Y/N)
, , (Y/N)
N
Fkt. Abt. AUS xxx Defrost functionality switched off during emergency power operation? (Y/N)
, , (Y/N)
N
Fkt. Lüft. AUS xxx Fans functionality switched off during emergency power operation? (Y/N)
, , (Y/N)
N
Fkt. Rhmhg.AUS xxx Frame heater functionality switched off during emergency power operation? (Y/N)
, , (Y/N)
N
Fkt. Licht AUS xxx Light functionality switched off during the emergency power operation? (Y/N)
, , (Y/N)
N