ABTAUUNG POS: XXXXX Input Default
Wartezeit XX m Setpoint wait time between cooling and defrost 0..15 0 m
Drip time x m Setpoint delay time (drip time) between defrost and cooling 0..15 0 m
Menu 2-2-2 Sollwerte Umsch.
ABTAUUNG POS: XXXXX Input Default
Abtauendtemp XX °C Setpoint defrost end temperature --, 0..20 8 °C
Wartezeit XX m Setpoint wait time between cooling and defrost 0..15 0 m
Drip time x m Setpoint delay time (drip time) between defrost and cooling 0..15 0 m
Menu 2-3
Not applicable for this controller type.
Menu 2-4 Alarm
ALARM POS: XXXXX
1 Setpoints Continue to menu 2-4-1
2 Sollwerte Umsch. Continue to menu 2-4-2
is not displayed when toggle setpoint is deactivated (menu 3-3)
Menu 2-4-1 Setpoints
ALARM POS:
XXXXX
Input Default
Soll Übertemp.
XX °C
High temperature setpoint at which the is tripped.
high temperature alarm
0..30 10 °C
Soll Untertmp. XX
K
Setpoint temperature (difference below the setpoint of the temperature regulation) at which the
low
alarm is tripped
temperature
--, 0..
6
4 K
Menu 2-4-2 Sollwerte Umsch.
ALARM POS:
XXXXX
Input Default
Soll Übertemp.
XX °C
High temperature setpoint at which the is tripped.
high temperature alarm
0..30 10 °C
Soll Untertmp. XX
K
Setpoint temperature (difference below the setpoint of the temperature regulation) at which the
low
alarm is tripped
temperature
--, 0..
6
4 K
Menu 2-5 Frame heater
RAHMENHEIZ POS: XXXXX
1 Frame heater mode Continue to menu 2-5-1
2 Frame heater setpoints Continue to menu 2-5-2
3 Toggle mode Continue to menu 2-5-3
is not displayed when toggle setpoint is deactivated (menu 3-3)
4 Sollwerte Umschal Continue to menu 2-5-4
is not displayed when toggle setpoint is deactivated (menu 3-3)
Selection list 2-5-1 Frame heater mode
The value is selected in accordance with the entry. The check mark indicates the current setting.