KGL Operating Manual – UA 412 S 2019-01-14 /92 122
Menu 3-2 Defrost timer
ABTAUUHR
POS: XXXXX
Input Default
Abtauuhr XXX Type of defrost initiation via input D11/12 (EXT) or internal (INT)
, , (EXT, INT)
INT
Sicherheitsz.
XXX m
Safe defrost time for the maximum permitted duration of the defrost (only
applicable for the internal defrost)
0..120 60 min
man. Abtauung
XXX
State (OFF/ON) for an additional manual defrost *) - only displayed if parameter
Abtauuhr = INT
, , (OFF/ON)
OFF
Abt.Uhr Z2 Separate defrost timer for zone 2 Menu 3-2-a
Abtau 1 xxxxx hh:
mm
Start time for the defrost with internal defrost; day of the week, time; - only
displayed if parameter Abtauuhr = INT
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
05:00
Abtau 2 xxxxx hh:
mm
Start time for the defrost with internal defrost; day of the week, time; - only
displayed if parameter Abtauuhr = INT
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
7:00
AM
Abtau 3 xxxxx hh:
mm
Start time for the defrost with internal defrost; day of the week, time; - only
displayed if parameter Abtauuhr = INT
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
1:00
PM
...
Abtau 14 xxxxx
hh:mm
*) The parameter is automatically set to ON after the first start for the duration of the safe defrost
time.
Menu 3-3 Sollw. Umschaltung
UMSCHALTNG
POS: XXXXX
Input Default
Status XXX Status (OFF/ON) of the toggle setpoint for the alternative setpoint set (toggle
setpoint set)
Sollumschaltg.
XXX
Type of the toggle setpoint usng:-
EXT = external via digital input D21/22-
INT = internal clock-
CAN = CAN bus - "--"= deactivated toggle setpoint
, , (EXT, INT, CAN, --)
EXT
Laufzeit Rollo X s Time for switching off fan and cooling after changeover to the alternative setpoint
set for external toggle setpoint (menu 3-3)
0..250 50 sec
Um EIN TT-TT hh:
mm
Start time of the changeover to the alternative setpoint set;
weekday from-to TT-TT, time hh:mm; only displayed for active internal toggle
setpoint (menu 3-3)
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
21:00
Um AUS TT-TT
hh:mm
End time of the changeover to the alternative setpoint set;
weekday from-to TT-TT, time hh:mm; only displayed for active internal toggle
setpoint (menu 3-3)
, , (Mon-Sun etc.) or
numbers (hh:mm)
Mon-
Sun
5:00
AM
Um EIN TT-TT hh:
mm
Start time of the changeover to the alternative setpoint set;
weekday from-to TT-TT, time hh:mm; only displayed for active internal toggle
setpoint (menu 3-3)
, , (Mon-Sun etc.) or
numbers (hh:mm)
Sun
05:00