KGL Operating Manual – UA 412 S 2019-01-14 /97 122
Menu 6-3 Cooling
KÜHLUNG POS:
XXXXX
Input Default
min. Laufzeit XX K Minimum run time of the cooling 0..15 5 m
min. Standzeit XX m Minimum switch-off time of the cooling 0..15 5 m
Dauerl.überw. XX m Time for the forced interruption of the cooling during continuous operation --, 0..
15
7 m
Notbetrieb XX m If necessary sensors for the regulation fail, the solenoid valve is actuated with the opening degree in
[%]set here.
0..100 40%
Menu 6-4 - Language
SPRACHEPOS: XXXXX Input Default
Deutsch D
English GB
Français F
Menu 6-5 Alarm priorities
ALARMPRIOSPOS: XXXXX Input Default
Kühlstellenprio X Priority of the alarms can be set
globally using the refrigeration point
priority (menu 6-1) (Y)
,
,
(Y,
N)
N
Priority: XX Display of refrigeration point priority
(menu 6-1)
only displayed if Kühlstellenprio is set
to Y
The following priorities are only displayed ig Kuhlstellenprio is set to N. The possible
entries for the priority of the alarms have the following meanings:
-=Event is ignored
0=Message (only entry in message list) 1=Alarm with priority 1 .. 99=Alarm with
priority 99
Low temp. Lower alarm temperature limit value
undercut; priority is applicable for all
messages
low-temp. zone 1, low-temp.
zone 2
-, 0..
99
0
High temp Upper alarm temperature limit value
exceeded; priority is applicable for all
messages
high-temp. zone 1, high-
temp. zone 2
-, 0..
99
1
Sensor fault Temperature sensor failed -, 0..
99
0
No Defrost No defrost within the alarm delay time
Priority is applicable for the message
No Defrost
-, 0..
99
0
Timer-Term. Defrost Defrost ended by safe defrost time -, 0..
99
0
Power failure Start-up after power failure -, 0..
99
0
First start
0