Interface COM1/Modem
TheCOM1interfaceisconfiguredinthisscreen.TheCOM1interfacecanbeusedasmodemoras
COM port server. When the interface is used as COM port server, the serial interface of the GLT 3010 can be
accessed via the Ethernet connection of the Virtus 5.
Use of the interface as modem
Interface - COM1/Modem Input Default
Telephone number Telephone number of the modem at the system
centre (connected to COM1)
max. 19 characters -
Dialling prefix Number for the outside line max. 8 digits -
MSN 19-digit terminal device identification number
- for direct outside line, this is the telephone
number (without the dialling prefix))
- in the normal case (i.e. for extensions), this is
the direct dial number
max. 19 characters 0
PIN PIN -
Alarm if modem not available Should an alarm be signalled if the modem is
not detected?
If the check mark is set and no modem is
detected at the interface,
the alarm "Modem Fault" is output after 2
minutes.
Y/N Y
Use of the interface as COM port server
Interface - COM1 / COM port
server
Input Default
TCP port Input of the TCP/IP port of the COM
port server
Numbers (1..65535) 1041
Baud rate Baud rate of the serial connection to the
GLT 3010
300, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 115200
38400
For detailed information, see chapter GSM modem.
For detailed information, see chapter COM Port Server.