177/183
Temperature change Transport: max. 20 K/h
Operation: max. 10 K/h
Relative humidity
(non-condensing)
Transport: 8% ... 80%
Operation: 20 % ... 80%
Shock
according to DIN EN
60068-2-27
Transport and operation: 10 g
Altitude Transport and operation: 0..2000 m
Standards and Directives
Protection rating Front with rubber seal: IP54
Panel mounting inside: IP20 (EN 60529)
CE conformity according
to
(see
https://edp.eckelmann.de/
edp/lds/_m3OjU2YOg1)
Low Voltage Directive 2014/35/EU;
Official Journal of the EU L96, 29/03/2014, pages 357-374
EMC Directive 2014/30/EU;
Official Journal of the EU L96, 29/03/2014, pages 79-106
RoHS Directive 2011/65/EU;
Official Journal of the EU L174, 01/07/2011, pages 88-11
DANGER
1)
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connection, it
must be checked that no voltage is present at the 230 V AC digital inputs and 230 V AC relay
outputs! Low voltage and safety extra-low voltage must not be applied together at the digital inputs A1/
A2 and B1/B2 and the relay outputs 15/16/18, 25/26/28 and 35/36/38! Rating data of the insulation of
the outer power circuits:
Rated insulation voltage: 300 V AC
Test voltage (L to PE): 1500 V AC
Safe electrical isolation