BA * PMC-2 * EN * 01/98 Page 29
4.4 Wiring notes
4.4.1 General
The wiring has to be done with regard to minimum cross sections, shields and earthings given.
Observe the presented branching conditions. If there are, for example, two parallel transmissions
starting from one point, it will not be admissible to lay only one transmission and to branch the one on
a later point, because induction loops (disturbance sender and aerials) as well as interfering potential
shift could develop.
ELAU as a system supplier provides the ready-made cables.
CAUTION
Minimum bending radius for all ELAU cables is 10 times the cable diameter
If no ELAU cables are used, please watch the following cross sections:
Admissible cable cross sections in dependence of current (VDE 0113), installation type C:
1,5 mm
2
up to 15A
2,5 mm
2
up to 21A
4 mm
2
up to 28A
PMC-2 type 4A 5A 8A 16A 25A
Mains cable in mm
2
1.5 1.5 1.5 2.5 4
Earth conductor to
the ZEP in mm
2
10 10 10 10 10
Control signals in
mm
2
0.5 0.5 0.5 0.5 0.5
DC-Circuit in mm
2
2.5 2.5 2.5 4 4
external bleeder in
mm
2
1.5 1.5 1.5 2.5 2.5
Motor type SB-070 SB-105 SB-145 SB-205
Motor cable in mm
2
1.5 1.5 1.5 / 2.5 / 4 2.5 / 4
The following cables have to be separately laid and shielded:
motor cable
resolver cable
encoder cable
serial interface
Check the wiring before the switch on.
To avoid errors we recommend you to order the connecting cables together
with the PMC-2.
Frequent errors are:
wrong shielding of transmissions
frame or earth circuits
change by mistake of the motor phases
change by mistake of the resolver connections