Instruction Manual PMC-2
BA * PMC-2 * EN * 01/98 Page 31
Motor cable 0 - 10m 10 - 20m 20 - 40m over 40m
SB056
mains filter
motor filter
no
no
(up to 25m)
FI07838
no
(up to 50m)
FI07838
FI07837
application
specific
filters (from 50m)
SB070
mains filter
motor filter
no
no
(up to 25m)
FI07838
no
(up to 50m)
FI07838
FI07837
application
specific
filters(from 50m)
SB105
mains filter
motor filter
no
no
FI07838
no
FI07838
FI07837
application
specific
filters
SB145 with PMC-2/8A
mains filter
motor filter
no
no
no FI07838
FI07837
application
specific
filters
SB145 from PMC-2/16A
mains filter
motor filter
no
no
no FI07841
FI07840
application
specific
filters
SB205
mains filter
motor filter
no
no
FI07841
no
FI07841
FI07840
application
specific
filters
Notes::
For groupwise shielding the common mains filter is dimensioned in such a way that I
Nominal
filter sum
I
Nominal
PMC-2.
The motor filter is to be mounted above or to the side of the PMC-2.
The motor filter is to be mounted as close as possible to the PMC-2. For cable lengths of less than 0.5
m between filter and PMC-2 no shielding is necessary between filter and PMC-2. Twist the motor
cable! The shield is guided directly from the motor cable to the central earthing point!
CAUTION
For cable lengths over 40 (or 50) metres please contact our application
department.