Refrigeration Control Modes Software Overview • 29
10.3.4.2. Configuring Controllers for Superheat and Suction Mode
To configure the controller as a master in the Superheat and Suction mode, the following parameters must be set:
Note that if the Modbus address or baud rate is changed, the controller must be rebooted
.
To configure the controller as a slave case controller in a lineup where the master controller is Superheat and Suction mode, the following
parameters must be set:
Parameter Description Parameter Value for Master
Controller
CrE Control Type Superheat and Suction
SSCP Superheat and suction control probe selection User choice, Average Lineup
Recommended
EEVCnt Number of EEVs in the case 0-3
StandaloneCC Yes = Controller is standalone (no lineup)
No = Controller is a master or slave in a lineup
NO
XEV20D-1 V1 Valve assigned to XEV20-1 valve output 1 EEPR
S1Addr Modbus address of slave device 1 2 if 1 slave CC is present; otherwise set at 0
S2Addr Modbus address of slave device 2 3 if 2 slave CC are present; otherwise set at 0
S3Addr Modbus address of slave device 3 4 if 3 slave CC are present; otherwise set at 0
S4Addr Modbus address of slave device 4 5 if 4 slave CC are present; otherwise set at 0
S5Addr Modbus address of slave device 5 6 if 5 slave CC are present; otherwise set at 0
Modbus_Addr Modbus address of this controller 1
Baud Baud of Modbus communication 19200
Table 10-4 - Master Controller Configurations for Superheat and Suction Control Mode
Parameter Description Parameter Value for Master
Controller
CrE Control Type Superheat only
SSCP Superheat and suction control probe selection User choice, Average Lineup
Recommended
EEV EEV driver XEV20
EEVCnt Number of EEVs in the case 0-3
StandaloneCC Yes = Controller is standalone (no lineup)
No = Controller is a master or slave in a lineup
NO
XEV20D-1 V1 Valve assigned to XEV20-1 valve output 1 EEPR
S1Addr Modbus address of slave device 1 0
S2Addr Modbus address of slave device 2 0
S3Addr Modbus address of slave device 3 0
S4Addr Modbus address of slave device 4 0
S5Addr Modbus address of slave device 5 0
Modbus_Addr Modbus address of this controller Set based on the S1-S5Addr of the master
CC
Baud Baud of Modbus communication 19200
Table 10-5 - Slave Controller Configurations Where Master is Superheat and Suction Mode