Commissioning the Device in E2E iPro Parameter List • 61
16 iPro Parameter List
Parameter Name Description Range
Fan Parameters
FOp Fan Operation Mode: OnR-OfD-Fan on with refrigeration off
defrost. OnR-OnD-Fan on Refrigeration on defrost. OnF-OfD-Fan on
continuously off defrost. OnF-OnD-Fan on continuously, on
defrost.
OnR-OfD, OnR-OnD, OnF-OfD,
OnF-OnD
FAd Fan After Defrost: Temperature-Activate after defrost based on Fst,
Fhy. Time-Activate after defrost based on Ftd.
Temperature/Time
FSt Fan Temp Setpoint -10-70°
FHy Fan Temp Hysteresis 1-30°
Ftd Fan Time Delay 0:00-10:00 minutes
FanAmpOn Amps required for Fan status to be considered ON 0-60 amps
FanAmpDel Time delay for status change once amps reach threshold 1-90 seconds
Alarm Parameters
ALU Maximum control temperature alarm, relative to active setpoint 0-99° above setpoint
ALL Minimum control temperature alarm, relative to active setpoint -99-0° below setpoint
AHy Alarm hysteresis 0-20°
ALd Alarm delay time before displaying alarm active 0-255 minutes
SHF% Superheat Control Temp failure-position valve is driven to in the
event of superheat reading failure
0-100%
SCF% Suction Control Temp failure-position the valve is driven to in the
event of control temperature failure
0-100%
Analog Input Parameters
AIC01 Configuration of Probe 1
Discharge 1-6, Return 1-3, Defrost Term
1-6, Coil Out 1-3, Pressure 1-3, Fan
Amperage, Defrost Amperage
AIC02 Configuration of Probe 2
AIC03 Configuration of Probe 3
AIC04 Configuration of Probe 4
AIC05 Configuration of Probe 5
AIC06 Configuration of Probe 6
AIC07 Configuration of Probe 7
AIC08 Configuration of Probe 8
AIC09 Configuration of Probe 9
AIC10 Configuration of Probe 10
Table 16-1 - iPro Parameter List