Commissioning the Device in E2E iPro Parameter List • 63
ddr Defrost Duration 1-360 Minutes
MinD Defrost minimum Time 1-60 Minutes
dEd Defrost Delay-Amount of time before activation of defrost relay 0-30 Minutes
dtT Defrost Termination Type Temp/Time
dPC Defrost Termination Temp Combination Avg/Min/Max
dSt Defrost Termination Setpoint 0-99°
DpT Dripping Time 0-30 Minutes
MWT Max Wait Time 0-60 Minutes
dTS Defrost Termination Temperature Selection Defrost Term Sensor/Coil Out Sensor/
Discharge Air
SHDef% SH valve defrost operation (XEV20 only) 0% or 100%
SuctionDef% Suction valve defrost operation 0% or 100%
MinI Minimum time between 2 starts of defrost 1-255 Minutes
SchHour Schedule defrost start (Hour) 0-23 Hour
SchMin Schedule defrost start (Minute) 0-59 Minute
SchPerDay Schedule defrost per day 1-12 Per Day
DefrAmpOn Amps required for Defrost status to be considered ON 0-60 Amps
DefrAmpDel Time delay for status change once amps reach threshold 1-90 Seconds
iPro Digital Input Parameters
DIC01 Configuration of Digital Input 1
Defrost Initiation/Door Switch/Clean
Switch/Dual Temp/Enable/Aux 1/Aux 2
DIC02 Configuration of Digital Input 2
DIC03 Configuration of Digital Input 3
DIC04 Configuration of Digital Input 4
DIC05 Configuration of Digital Input 5
DIC06 Configuration of Digital Input 6
DIC07 Configuration of Digital Input 7
DIC08 Configuration of Digital Input 8
DIC09 Configuration of Digital Input 9
DIC10 Configuration of Digital Input 10
DIC11 Configuration of Digital Input 11
DIC12 Configuration of Digital Input 12
DIC13 Configuration of Digital Input 13
DIC14 Configuration of Digital Input 14
DIC15 Configuration of Digital Input 15
DIC16 Configuration of Digital Input 16
DIC17 Configuration of Digital Input 17
DIC18 Configuration of Digital Input 18
DIC19 Configuration of Digital Input 19
DIC20 Configuration of Digital Input 20
Table 16-1 - iPro Parameter List