GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 21
Guidelines for Mounting (IP66 Units)
Before mounting the drive, ensure that the chosen location meets the environmental condition
requirements for the drive shown in section Environmental on page 84.
The drive must be mounted vertically, on a suitable at surface.
The minimum mounting clearances as shown in the table below must be observed.
The mounting site and chosen mountings should be sufcient to support the weight of the drives.
Using the drive as a template, or the dimensions shown below, mark the locations required for drilling.
Suitable cable glands to maintain the ingress protection of the drive are required. Gland holes for power
and motor cables are pre-moulded into the drive enclosure, recommended gland sizes are shown below.
Gland holes for control cables may be cut as required.
Figure 12: IP66 Adequate Mounting Clearances
Table 16: IP66 Adequate Mounting Clearances
Drive
Size
X – Above & Below Cable Gland Sizes
mm in Frame Power Cable Motor Cable Control Cables
2 & 3 200 7.87 2 & 3 PG21 (M25) PG21 (M25) PG13.5 (M20)
NOTE
Typical drive heat losses are approximately 3% of operating load conditions.
Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times.
Alternative metric gland sizes are shown in the brackets.