50 PACMotion VFD AC Variable Speed Drive User Guide GFK-3111A
Digital Input Conguration Parameter P1-13
Table 28: Digital Input Conguration Parameter P1-13
P1-13 DI1 DI2 DI3 AI1 / DI4 AI2 / DI5
State 0 1 0 1 0 1 0 1 0 1
0
User dened
1
STOP RUN
FWD
REV P1-12 REF P2-01 Analog Input AI1 P2-01 P2-02
2
STOP RUN
FWD
REV
DI3 DI4 DI5 Preset Speed
0 0 0 P2-01 REF
1 0 0 P2-02 REF
0 1 0 P2-03 REF
1 1 0 P2-04 REF
0 0 1 P2-05 REF
1 0 1 P2-06 REF
0 1 1 P2-07 REF
1 1 1 P2-08 REF
3
STOP RUN
FWD
REV P1-12 REF P2-01 REF Analog Input AI1 Analog Input AI2
4
STOP RUN
FWD
REV P1-12 REF P2-01 REF Analog Input AI1 DECEL
P1-04
DECEL
P8-11
5
STOP RUN
FWD
REV P1-12 REF AI2 REF Analog Input AI1 Analog Input AI2
6
STOP RUN
FWD
REV P1-12 REF P2-01 REF Analog Input AI1 E-TRIP OK
7
STOP RUN
FWD
REV
DI3 DI4 Preset Speed
E-TRIP OK
Off Off P2-01 REF
On Off P2-02 REF
Off On P2-03 REF
On On P2-04 REF
8
STOP RUN
FWD
REV
DI3 DI4 Preset Speed
DECEL
P1-04
DECEL
P8-11
Off Off P2-01 REF
On Off P2-02 REF
Off On P2-03 REF
On On P2-04 REF
9
STOP RUN
FWD
REV
DI3 DI4 Preset Speed
P1-12 REF PR-REF
Off Off P2-01 REF
On Off P2-02 REF
Off On P2-03 REF
On On P2-04 REF
10
STOP RUN
FWD
REV (NO) INC SPD (NO) DEC SPD P1-12 REF
1
P2-01-REF
11
STOP RUN FWD
STOP RUN REV
P1-12 REF PR-REF Analog Input AI1 P2-01 REF P2-02 REF
12
STOP RUN FWD
STOP RUN REV
DI3 DI4 DI5 Preset Speed
Off Off Off P2-01 REF
On Off Off P2-02 REF
Off On Off P2-03 REF
On On Off P2-04 REF
Off Off On P2-05 REF
On Off On P2-06 REF
Off On On P2-07 REF
On On On P2-08 REF
13
STOP RUN FWD
STOP RUN REV
P1-12 REF P2-01 REF Analog Input AI1 Analog Input AI2