GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 41
Selecting the Language on the TFT and OLED Display
VFD 01 Select Language Select Language
STOP
Español
Deutsch
English
Español
Deutsch
English
15 kW
400 V
3 Ph
Hold down the
Start and Up keys
for >1s.
Use the Up and
Down arrows to
select a language.
Press the Navigate
button to select.
Operating Displays
Inhibit /
STO Active
Drive Stopped Drive Running
Output Freq
Display
Drive Running
Output Current
Display
Drive Running
Motor Power
Display
Drive Running
Motor Speed
Display
TFT and OLED Display :
VFD 01 VFD 01
Output Frequency 01
Motor Current 01 Motor Power 01 Motor Speed 01
INHIBIT STOP 23.7 Hz 15.3 A 6.9 kW 718 rpm
15 kW 400 V 3 Ph 15 kW 400 V 3 Ph 15.3 A 6.9 kW 6.9 kW 23.7 Hz 23.7 Hz 15.3 A 23.7 Hz 15.3 A
Drive Inhibited.
The STO
connections are
not made. Refer
to section
Figure 28:
Recommended
“STO” Wiring on
page 38.
Drive Stopped /
Disabled.
Drive is enabled /
running, display
shows the output
frequency
(Hz). Press the
Navigate key to
select alternative
displays.
Press the Navigate
key for < 1 second.
The display will
show the motor
current (Amps).
Press the Navigate
key for < 1 second.
The display will
show the motor
power (HP).
If P1-10 > 0,
pressing the
Navigate key for
< 1 second will
display the motor
speed (RPM).
Additional Display Messages
Auto Tuning in
Progress
External 24V DC
Supply
Overload Switching Freq
Display
Mains Loss Maintenance
Time Elapsed
TFT and OLED Display :
VFD 01 VFD 01 VFD 01 VFD 01 VFD 01
Auto-tuning
Ext 24 V
OL
23.7 Hz
SF
23.7 Hz
ML
23.7 Hz 23.7 Hz
External 24V mode
15.3 A 6.9 HP 15.3 A 6.9 HP 15.3 A 6.9 kW 15.3 A 6.9 kW
Auto tune in
progress. See
parameter P4-02
information in
section Parameter
Group 4 – High
Performance
Motor Control on
page 63.
The drive control
board is powered
only from an
external 24 Volt
source, with no
mains power
applied.
Indicates an
Overload
condition. Output
current exceeds
the motor rated
current entered in
Parameter P1-08.
Switching
frequency is
reduced, due to
high heatsink
temperature.
The incoming
mains power
supply has been
disconnected or is
missing.
The user
programmable
maintenance
reminder time has
elapsed.