28 PACMotion VFD AC Variable Speed Drive User Guide GFK-3111A
Motor Terminal Box Connections
Most general purpose motors are wound for operation on dual voltage supplies. This is indicated on the
nameplate of the motor. This operational voltage is normally selected when installing the motor by selecting
either STAR or DELTA connection. STAR always gives the higher of the two voltage ratings.
Table 17: Motor Terminal Box Connections
Incoming Supply Voltage Motor Nameplate Voltages Connection
230 230 / 400
Delta
400 / 460 400 / 690
575 575 / 1000
400 230 / 400
Star
575 330 / 575
Connecting a Brake Resistor
PACMotion VFD units feature an internal brake transistor, tted as standard for all models. The brake resistor
should be connected to the DC+ and BR terminals of the drive. These terminals are shrouded, and the
shrouding should be removed to access the terminals.
Figure 20: IP20 Drive Models Figure 21: IP55 & IP66
Frame Sizes 2, 3, 4 & 5
Remove the plastic cover from the
base of the drive as indicated.
Frame Sizes 6A/ 6B
Remove the plastic cover from
inside the drive as indicated.
EMC EMC VA R
AC DC
All frame sizes
Remove the plastic cover from
inside the drive as indicated.
L1
L3
EMC
L2/N
UVW
1 2 3 4 5 6 7 8 9
10
11
12
13
14 15 16 17 18
I0I0II0I0I
The brake transistor is enabled using P1-05 (Refer to section Parameter Group 1 – Basic Parameters on page