GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 61
Parameter Group 3 – PID Control
Overview
PACMotion VFD provides an internal PID controller. Parameters for conguration of the PID controller are
located together in Group 3. For simple applications, the user needs to only dene the setpoint source (P3-05
to select the source or P3-06 for a xed setpoint), feedback source (P3-10) and adjust the P Gain (P3-01),
I time (P3-02) and optionally the differential time (P3-03).
The PID operation is uni-directional, and all signals are treated as 0 – 100% to provide a simple, intuitive
operating format.
Table 37: Parameter Group 3 – PID Control
Par Parameter Name Minimum Maximum Default Units
P3-01 PID proportional gain 0.0 30.0 1.0 -
PID Controller Proportional Gain. Higher values provide a greater change in the drive output frequency in
response to small changes in the feedback signal. Too high a value can cause instability.
P3-02 PID integral time 0.0 30.0 1.0 s
PID Controller Integral Time. Larger values provide a more damped response for systems where the overall
process responds slowly.
P3-03 PID differential time 0.00 1.00 0.00 s
PID Differential Time Constant.
P3-04 PID operating mode 0 1 0 -
0 Direct Use this mode if an increase in the motor speed should result in an
increase in the feedback signal.
1 Inverse Use this mode if an increase in the motor speed should result in a
decrease in the feedback signal.
P3-05 PID reference select 0 2 0 -
0 Digital preset P3-06 is used.
1 Analog Input 1 Analog Input 1 as displayed in P0-01 is used.
2 Analog Input 2 Analog Input 2 as displayed in P0-02 is used.
P3-06 PID digital reference 0.0 100.0 0.0 %
When P3-05 = 0, this parameter sets the preset digital reference (setpoint) used for the PID Controller.
Where the feedback is provided from a transducer such as a pressure transducer or level measurement,
this represents the percentage of the pressure range (e.g. for a 0 – 10 Bar transducer, 4 bar = 40%) or the
level.
P3-07 PID output upper limit P3-08 100.0 100.0 %
Limits the maximum value output from the PID controller.
P3-08 PID output lower limit 0.0 P3-07 0.0 %
Limits the minimum output from the PID controller.
P3-09 PID output limit select 0 3 0 -
0 Digital Output Limits The output range of the PID controller is limited by the values of P3-07
& P3-08.
1 Upper limit set by analog
input 1
The output range of the PID controller is limited by the values of P3-08
& the signal applied to Analog Input 1.
2 Lower limit set by analog
input 1
The output range of the PID controller is limited by the signal applied to
Analog Input 1 & the value of P3-07.
3 PID output added to analog
input 1
The output value from the PID Controller is added to the speed
reference applied to the Analog Input 1.
P3-10 PID feedback select 0 5 0 -
0 Analog Input 2
1 Analog Input 1
2 Motor Current
3 DC Bus Voltage
4 Differential : Analog Input 1 – Analog Input 2
5 Largest Value : Analog Input 1 or Analog Input 2