30 PACMotion VFD AC Variable Speed Drive User Guide GFK-3111A
Control Terminal Wiring
All analog signal cables should be suitably shielded. Twisted pair cables are recommended.
Power and Control Signal cables should be routed separately where possible, and must not be routed
parallel to each other.
Signal levels of different voltages e.g. 24 Volt DC and 110 Volt AC, should not be routed in the same cable.
Maximum control terminal tightening torque is 0.5 Nm.
Control Cable entry conductor size: 0.05 – 2.5mm2 / 30 – 12 AWG.
Figure 23: Control Connections
+
_
2 (Dl 1)
1 (+24 V DC/ 100mA)
5 (+10V DC/ 10 mA)
6 (AI 1/ DI 4*)
10 (AI 2/ DI 5*)
14 (RL1-C)
(AO 1) 8
(0 V/ COM) 9
0-10 V
10-0 V
0/4-20 mA
20-4/0 mA
0-10 V
10-0 V
0/4-20 mA
20-4/0 mA
0-10 V
10-0 V
-10 ...10 V
0/4-20 mA
20-4 mA
+24 V DC**
0-10 V
10-0 V
-10 ...10 V
0/4-20 mA
20-4 mA
(AO 2) 11
15 (RL1-NO)
16 (RL1-NC)
17 (RL2-A)
18 (RL2-B)
12 (STO+)
NOTE
* Dashed lines shows connection for analog inputs in digital mode
** Optional external 24 V DC power supply
13 (STO-)
7 (0V/ COM)
3 (Dl 2)
4 (Dl 3)