GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 57
Par Parameter Name Minimum Maximum Default Units
P2-13 Analog output AO2 function 0 12 9 -
Digital Output Mode. Logic 1 = +24 V DC
0 Drive running Logic 1 when the PACMotion VFD is enabled (Running).
1 Drive healthy Logic 1 When no Fault condition exists on the drive.
2 At speed Logic 1 when the output frequency matches the setpoint frequency.
3 Motor speed > 0 Logic 1 when the motor runs above zero speed.
4 Motor speed >= limit Logic 1 when the motor speed exceeds the adjustable limit.
5 Motor current >= limit Logic 1 when the motor current exceeds the adjustable limit.
6 Motor torque >= limit Logic when the motor torque exceeds the adjustable limit.
7 Analog input 2 >= limit Logic when the signal applied to the Analog Input 2 exceeds the
adjustable limit.
Note When using settings 4 – 7, parameters P2-19 and P2-20 must be used together to control the behaviour.
The output will switch to Logic 1 when the selected signal exceeds the value programmed in P2-19, and
return to Logic 0 when the signal falls below the value programmed in P2-20.
Analog Output Mode
8 Motor speed 0 to P1-01.
9 Motor current 0 to 200% of P1-08.
10 Motor torque 0 to 200% of motor rated torque.
11 Motor power 0 to 150% of drive rated power.
12 PID output Output from the internal PID Controller, 0 – 100%.
P2-14 Analog output AO2 format See Below 0-10 Volt -
0-10 volt
0 to10 V
10-0 volt
10 to 0 V
0-20 mA 0 to 20 mA
20-0 mA 20 to 0 mA
4-20 mA 4 to 20 mA
20-4 mA 20 to 4 mA
P2-15 Relay 1 function 0 14 1 -
Setting Function Logic 1 when
0 Drive running The PACMotion VFD is enabled (Running).
1 Drive healthy No fault or trip condition exists on the drive.
2 At speed Output frequency matches the setpoint frequency.
3 Motor speed > 0 The motor runs above zero speed.
4 Motor speed >= limit The motor speed exceeds the adjustable limit.
5 Motor current >= limit The motor current exceeds the adjustable limit.
6 Motor torque >= limit The motor torque exceeds the adjustable limit.
7 Analog input 2 >= limit The signal applied to the Analog Input 2 exceeds the adjustable limit.
8 Reserved No Function.
9 Reserved No Function.
10 Maintenance due The internally programmable maintenance timer has elapsed.
11 Drive ready to run 0 to 150% of drive rated power.
12 Drive tripped The drive is not tripped, the STO circuit is closed, the mains supply is
present and the hardware enable input present (Digital Input 1 unless
changed by the user).
13 STO status When both STO inputs are present and the drive is able to be operated.
14 PID error >= limit The PID Error (difference between setpoint and feedback) is greater than
or equal to the programmed limit.
Note When using settings 4 – 7 and 14, parameters P2-16 and P2-17 must be used together to control the
behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in
P2-16, and return to Logic 0 when the signal falls below the value programmed in P2-17.
P2-16 Relay 1 / AO1 upper limit P2-17 200.0 100.0 %
P2-17 Relay 1 / AO1 lower limit 0.0 P2-16 0.0 %
Used in conjunction with some settings of Parameters P2-11 & P2-15.