EasyManua.ls Logo

Emerson PACMotion VFD Series - Page 57

Emerson PACMotion VFD Series
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 57
Par Parameter Name Minimum Maximum Default Units
P2-13 Analog output AO2 function 0 12 9 -
Digital Output Mode. Logic 1 = +24 V DC
0 Drive running Logic 1 when the PACMotion VFD is enabled (Running).
1 Drive healthy Logic 1 When no Fault condition exists on the drive.
2 At speed Logic 1 when the output frequency matches the setpoint frequency.
3 Motor speed > 0 Logic 1 when the motor runs above zero speed.
4 Motor speed >= limit Logic 1 when the motor speed exceeds the adjustable limit.
5 Motor current >= limit Logic 1 when the motor current exceeds the adjustable limit.
6 Motor torque >= limit Logic when the motor torque exceeds the adjustable limit.
7 Analog input 2 >= limit Logic when the signal applied to the Analog Input 2 exceeds the
adjustable limit.
Note When using settings 4 – 7, parameters P2-19 and P2-20 must be used together to control the behaviour.
The output will switch to Logic 1 when the selected signal exceeds the value programmed in P2-19, and
return to Logic 0 when the signal falls below the value programmed in P2-20.
Analog Output Mode
8 Motor speed 0 to P1-01.
9 Motor current 0 to 200% of P1-08.
10 Motor torque 0 to 200% of motor rated torque.
11 Motor power 0 to 150% of drive rated power.
12 PID output Output from the internal PID Controller, 0 – 100%.
P2-14 Analog output AO2 format See Below 0-10 Volt -
0-10 volt
0 to10 V
10-0 volt
10 to 0 V
0-20 mA 0 to 20 mA
20-0 mA 20 to 0 mA
4-20 mA 4 to 20 mA
20-4 mA 20 to 4 mA
P2-15 Relay 1 function 0 14 1 -
Setting Function Logic 1 when
0 Drive running The PACMotion VFD is enabled (Running).
1 Drive healthy No fault or trip condition exists on the drive.
2 At speed Output frequency matches the setpoint frequency.
3 Motor speed > 0 The motor runs above zero speed.
4 Motor speed >= limit The motor speed exceeds the adjustable limit.
5 Motor current >= limit The motor current exceeds the adjustable limit.
6 Motor torque >= limit The motor torque exceeds the adjustable limit.
7 Analog input 2 >= limit The signal applied to the Analog Input 2 exceeds the adjustable limit.
8 Reserved No Function.
9 Reserved No Function.
10 Maintenance due The internally programmable maintenance timer has elapsed.
11 Drive ready to run 0 to 150% of drive rated power.
12 Drive tripped The drive is not tripped, the STO circuit is closed, the mains supply is
present and the hardware enable input present (Digital Input 1 unless
changed by the user).
13 STO status When both STO inputs are present and the drive is able to be operated.
14 PID error >= limit The PID Error (difference between setpoint and feedback) is greater than
or equal to the programmed limit.
Note When using settings 4 – 7 and 14, parameters P2-16 and P2-17 must be used together to control the
behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in
P2-16, and return to Logic 0 when the signal falls below the value programmed in P2-17.
P2-16 Relay 1 / AO1 upper limit P2-17 200.0 100.0 %
P2-17 Relay 1 / AO1 lower limit 0.0 P2-16 0.0 %
Used in conjunction with some settings of Parameters P2-11 & P2-15.

Table of Contents

Other manuals for Emerson PACMotion VFD Series

Related product manuals