GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 65
Synchronous Reluctance (Syn RM) Motors
When operating with Synchronous Reluctance motors, carry out the following steps:
Ensure advanced parameter access is enabled by setting P1-14 = 101 (default value for security access).
Enter the motor nameplate details into the relevant parameters as follows:
o P1-07 Motor Rated Voltage.
o P1-08 Motor Rated Current.
o P1-09 Motor Rated Frequency.
o (Optional) P1-10 Motor Rated Speed (Rpm).
o P4-05 Motor Power Factor.
Select Synchronous Reluctance Motor Control mode by setting P4-01 = 6.
Ensure that the motor is correctly connected to the drive.
Carry out a motor data Autotune by setting P4-02 = 1.