EasyManua.ls Logo

Emerson PACMotion VFD Series - Page 77

Emerson PACMotion VFD Series
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 77
Figure 31: RS-485 Communications Electrical Connections
Modbus
RTU RS485
Controller
RS485+
RS485-
0 Volt / Common
Ground
NOTES
Use 3 or 4 Conductor Twisted
Pair Cable
•RS485+ and RS485- must be
twisted pair
Ensure the network taps for the drive
are kept as short as possible
•Terminate the network cable shield at
the controller only. Do not terminate
at
the drive!
0 Volt common must be connected
across all devices and to reference
0 Volt terminal at the controller
Do not connect the 0V Common
of the network to power ground
OPT-2-BNTSP- IN
12 3
RS485+
0 Volt / Common
Connection to the
drive through the
option
RS485-
Pin 3 –
0 Volt / Common
Pin 7 – RS485- (Modbus RTU)
Pin 8 – RS485+ (Modbus RTU)
RJ45 connector pinout
Direct connection to the drive
through the built-in RJ45 port
1 2 3 4 5 6 7 8
1
2
3
4
5
6
7
8
RS485+
RS485-
0 Volt / Common
Shield
Modbus RTU and CANbus connection should be made via the RJ45 connector. The pin assignments are as
shown above, in section RS-485 Communications.
Modbus RTU and CANbus networks require three conductors for best operation and to eliminate
common mode voltages on the drive terminals:
o RS485+
o RS485-
o 0 Volt Common
Connection should be made using a suitable dual twisted pair, shielded cable, with a wave impedance of
120 Ohms.
Use one of the twisted pairs to connect to the RS485+ and RS485- of each drive.
Use one conductor of the remaining pair to connect together all the 0 volt common connection
terminals.
The cable shield should be connected to a suitable clean ground point to prevent interference with the
screen maintained as close as possible to the cable terminations.
Do not connect the 0 Volt Common, RS485- or RS485+ to ground at any point.
Network terminating resistor (120 Ohms) should be used at the end of the network to reduce noise.

Table of Contents

Other manuals for Emerson PACMotion VFD Series

Related product manuals