GFK-3111A PACMotion VFD AC Variable Speed Drive User Guide 85
Table 57: 380 – 480 Volt (+ / - 10%), 3 Phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated Output
Current
Maximum Motor
Cable Length
Recommended
Brake Resistance
kW HP A
Non UL
UL mm AWG/kcmil A m ft Ω
2 0.75 1 3.5 6 6 8 8 2.2 100 330 400
2 1.5 2 5.6 10 10 8 8 4.1 100 330 200
2 2.2 3 7.5 10 10 8 8 5.8 100 330 150
2 4 5 11.5 16 15 8 8 9.5 100 330 100
3 5.5 7.5 17.2 25 25 8 8 14 100 330 75
3 7.5 10 21.8 32 30 8 8 18 100 330 50
3 11 15 27.5 40 35 8 8 24 100 330 40
4 15 20 34.2 50 45 16 5 30 100 330 22
4 18.5 25 44.1 63 60 16 5 39 100 330 22
4 22 30 51.9 63 70 16 5 46 100 330 22
5 30 40 66.1 80 80 35 2 61 100 330 12
5 37 50 77.3 100 100 35 2 72 100 330 12
6 45 60 102.7 125 125 150 300MCM 90 100 330 6
6A 45 60 83.5 125 110 150 300MCM 90 100 330 6
6 55 75 126.4 125 175 150 300MCM 110 100 330 6
6A 55 75 102.2 125 125 150 300MCM 110 100 330 6
6 75 100 164.7 200 200 150 300MCM 150 100 330 6
6B 75 100 144.1 200 175 150 300MCM 150 100 330 6
6 90 150 192.1 250 250 150 300MCM 180 100 330 6
6B 90 150 167.4 250 225 150 300MCM 180 100 330 6
6B 110 175 189.8 250 250 150 300MCM 202 100 330 6
7 110 175 210.8 250 300 150 300MCM 202 100 330 6
7 132 200 241.0 315 300 150 300MCM 240 100 330 6
7 160 250 299.0 400 400 150 300MCM 302 100 330 6
8 200 300 377.2 500 500 240 450MCM 370 100 330 3
8 250 350 458.7 600 600 240 450MCM 450 100 330 3
Table 58: 480 – 525 Volt (+/- 10%), 3 phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated Output
Current
Maximum Motor
Cable Length
Recommended
Brake Resistance
kW HP A
Non UL
UL mm AWG/kcmil A m ft Ω
7 132 192 250 150 300MCM 185 100 330 7
7 160 215 315 150 300MCM 205 100 330 7
7 185 262 315 150 300MCM 255 100 330 7
7 200 275 400 150 300MCM 275 100 330 7