10-9
Approvals Pending Hazardous Locations Certifications
Factory Mutual (FM) Approvals
(
Explosion Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G.
Dust-Ignition Proof for Class III, Division 1. NEMA 4X.
Factory-sealed.
,
Intrinsically safe for use in Class I, Division 1, Groups A, B, C, and
D; Class II, Division 1, Groups E, F, and G; Class III, Division 1
when connected in accordance with Rosemount drawings
03031-1019 and 00275-0081 (when used with HART
Communicator Model 275), or 00268-0031 (when used with
Rosemount Model 268 Communicator). Temperature Code T4.
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
NEMA 4X. Factory-sealed.
.
Combination of E5 and I5. NEMA 4X. Factory-sealed.
Canadian Standards Association (CSA)
&
Explosion Proof for Class I, Division 1, Groups C, and D.
Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G.
Dust-Ignition Proof for Class III, Division 1. Suitable for Class I,
Division 2, Groups A, B, C, and D. CSA Enclosure-Type 4X.
Factory-sealed.
Intrinsically safe for use in Class I, Division 1, Groups A, B, C, and
D when connected in accordance with Rosemount drawings
03031-1024. Temperature Code T3C. CSA Enclosure-Type 4X.
Factory-sealed.
FM Approved Entity Parameters
(1)
(1) When connected in accordance with Rosemount drawings 3031-1019 and 00275-0081 (for use
with the HART Communicator Model 275), or 00268-0031 (for use with the Rosemount Model 268
Communicator).
FM Approved for Class I, II, and III;
Division 1 and 2; Groups
V
Max
= 40 V dc
I
Max
= 165 mA
I
Max
= 225 mA
I
Max
= 160 mA (Option Code T1)
P
Max
= 1 W
C
I
= 0.01 F (Output Code A)
L
I
= 10 H
L
I
= 1.05 mH (Output Code A with T1)
A G
A G
C G
A G
A G
A G
A G
A G
CSA Approved
Barriers
(1)
(2)
(1) When connected in accordance with Rosemount drawings 00275-0082 and 3031-1024.
CSA Approved for Class I,
Division 1 and 2, Groups
Output
Code A
30 V,
330
W
28 ,
300
W
25 V,
200
W
22 ,
180
W
30 V,
150
W
Output
Code M
Supply
28V,
300
W
Return
10 V,
47
W
Supply
30 V,
150
W
Return
10 V,
47
W
A - D
C
-
D
A - D
C - D

Table of Contents