Product Certifications
March 2016
Reference Manual
00809-0100-4772, Rev FA
138
Product Certifications
4. Only be connected to the certified associated
apparatus, the Vortex Flowmeter could be used in the
explosive atmosphere. The connection should be
complied with the requirements of the manual of the
associated apparatus and the Vortex Flowmeter.
5. The enclosure should be taken to protect it from
impact.
6. Any friction should be prevented in order to avoid the
risk of electrostatic charge on the enclosure due to
non-conductive paint.
7. The cable with shield is suitable for connection, and
the shield should be connected to earth.
8. The enclosure shall be kept from the dust, but the
dust shall not be blown by compressed air.
9. The cable entry holes have to be connected by means
of suitable cable entry, the way of being installed shall
be ensure that the equipment satisfies degree of
protection IP66 according to GB4208-2008.
10. Users are forbidden to change the configuration to
ensure the explosion protection performance of the
equipment. Any faults shall be settled with experts
from the manufacturer.
11. Precautions shall be taken to ensure that the
electronic parts are within permissible ambient
temperature considering the effect of the allowed
fluid temperature.
12. During installation, operation and maintenance, users
shall comply with the relevant requirements of the
product instruction manual, GB3836.13- 1997
“Electrical apparatus for explosive gas atmospheres
Part 13: Repair and overhaul for apparatus used in
explosive gas atmospheres”, GB3836.15-2000
“Electrical apparatus for explosive gas atmospheres
Part 15: Electrical installations in hazardous areas
(other than mines)”, GB3836.16-2006 “Electrical
apparatus for explosive gas atmospheres Part 16:
Inspection and maintenance of electrical installation
(other than mines)”, and GB50257-1996 “Code for
construction and acceptance of electrical device for
explosion atmospheres and fire hazard electrical
equipment installation engineering”.
Type n certification
GB3836.1 – 2010
GB3836.4 – 2010
GB3836.8 – 2003
N3 Certification No. GYJ12.1107X
Ex nA ic IIC T5 Gc (- 50 °C T
a
+70 °C) 4-20 mA HART
Ex nA ic IIC T5 Gc (- 50 °C T
a
+60 °C) Fieldbus
Special conditions for safe use (X):
1. The maximum allowable length of the
interconnecting cable between transmitter and
sensor is 152 m. The cable shall also be provided by
the manufacturer.
2. Suitable heat-resisting cables rated at least +80 °C
shall be used when the temperature around the cable
entry exceeds +60 °C.
3. When transient protection terminal block (The Other
Option is T1) applied to this product, during
installation, users shall comply with Clause 12.2.4 in
GB3836.15-2000 “Electrical apparatus for explosive
gas atmospheres Part 15: Electrical installations in
hazardous areas (other than mines).
4. Any friction should be prevented in order to avoid the
risk of electrostatic charge on the enclosure due to
non-conductive paint.
5. Do not open when energized.
6. The cable entry holes have to be connected by means
of suitable cable entry, the way of being installed shall
be ensure that the equipment satisfies degree of
protection IP54 according to GB4208-2008.
7. Users are forbidden to change the configuration to
ensure the explosion protection performance of the
equipment. Any faults shall be settled with experts
from the manufacturer.
8. Precautions shall be taken to ensure that the
electronic parts are within permissible ambient
temperature considering the effect of the allowed
fluid temperature.
9. During installation, operation and maintenance, users
shall comply with the relevant requirements of the
product instruction manual, GB3836.13- 1997
“Electrical apparatus for explosive gas atmospheres
Part 13: Repair and overhaul for apparatus used in
explosive gas atmospheres”, GB3836.15-2000
“Electrical apparatus for explosive gas atmospheres
Part 15: Electrical installations in hazardous areas
(other than mines)”, GB3836.16-2006 “Electrical
apparatus for explosive gas atmospheres Part 16:
Inspection and maintenance of electrical installation
(other than mines)”, and GB50257-1996 “Code for
construction and acceptance of electrical device for
explosion atmospheres and fire hazard electrical
equipment installation engineering”.
Combined Chinese certifications (NEPSI)
K3 E3, I3, and N3 Combination
B.5.5 Brazilian certifications (INMETRO)
I. S. Certification
ABNT NBR IEC 60079-0: 2013
ABNT NBR IEC 60079-11: 2009
ABNT NBR IEC 60079-26: 2008 and 2009 correction
ABNT NBR IEC 60079-27: 2010
I2 Certification Number: NCC 11.0699 X
Ex ia IIC T4 Ga (-60 °C Ta + 70 °C) 4-20 mA HART
Ex ia IIC T4 Ga (-60 °C Ta + 60 °C) Fieldbus
Aotewell Ltd
www.aotewell.com