13
Reference Manual
00809-0100-4772, Rev FA
Configuration and Operation
March 2016
Configuration and Operation
2.7 Transducer Block
The Transducer Block contains sensor and process fluid information used by the transmitter
for accurate measurements.
2.7.1 Parameters
To make parameter changes, the Block Mode must be in the Out of Service (OOS) mode of
operation.
The Transducer Block parameters must be correct for an accurate measurement. These
parameters are factory configured specifically for the measurement when the transmitter is
sized using Rosemount Instrument Toolkit
™
program.
2.7.2 XMTR_MODE
Transmitter Mode
Without Temperature Sensor—No process temperature sensor available (Non MTA
electronics)
With Temperature Sensor—Process temperature sensor installed (MTA electronics only)
2.7.3 PROCESS_FLUID
Liquid—Process fluid is liquid
Gas/Steam—Process fluid is a gas
T Comp Sat Steam—Temperature Compensated Saturated Steam (MTA electronics only)
2.7.4 Reference K_FACTOR
The factory calibrated K-Factor stamped on the meter body
2.7.5 FIXED_PROC_TEMPERATURE
Fixed Process Temperature. The operating temperature of the process
2.7.6 FIXED_PROC_DENSITY
Fixed Process Density. The density of the process fluid at flowing pressure and temperature
2.7.7 FLANGE_TYPE
The flange rating and type to match the vortex meter body
2.7.8 PIPE_INSIDE_DIAMETER
The inside diameter (I.D.) of the mating pipe where the meter body is installed.
2.7.9 DAMPING
The flow damping value. Default is 2 seconds. Valid range is 0.2 to 255 seconds.