12
Reference Manual
00809-0100-4772, Rev FA
Configuration and Operation
March 2016
Configuration and Operation
1. Flow simulation mode
2. PWA simulation active
3. Low flow cutoff active
4. Flow signal injection
5. PV range exceeded
6. Sensor range exceeded
7. Process temp above USL (427 °C) (MTA only)
8. Process temp below LSL ( –50 °C) (MTA only)
9. Process temp above sat steam limit (MTA only)
10. Process temp below sat steam limit (MTA only)
ADVISE_MASK
The ADVISE_MASK parameter will mask any of the failed conditions listed in
ADVISE_ENABLED. A bit on means the condition is masked out from alarming and will not
be reported.
ADVISE_PRI
ADVISE_PRI designates the alarming priority of the ADVISE_ALM, see “Process alarms” on
page 17. The default is 0 and the recommended values are 1 or 2.
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays which of the advisories is active. Only the advisory
with the highest priority will be displayed. This priority is not the same as the ADVISE_PRI
parameter described above. This priority is hard coded within the device and is not user
configurable.
ADVISE_ALM
ADVISE_ALM is an alarm indicating advisory alarms. These conditions do not have a direct
impact on the process or device integrity.
Recommended actions for PlantWeb alarms
The RECOMMENDED_ACTION parameter displays a text string that will give a
recommended course of action to take based on which type and which specific event of the
PlantWeb alarms is active Table 5-1. Reference Index Number 78.