139
Product Certifications
Product Certifications
March 2016
Reference Manual
00809-0100-4772, Rev FA
IB Certification Number: NCC 11.0699 X
Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ + 60 °C)
Special conditions for safe use (X):
1. When fitted with 90V transient suppressors, the
equipment is not capable of passing the 500V
insulation test. This must be taken into account upon
installation.
2. The enclosure may be made from aluminum alloy
with a protective polyurethane paint finish; however,
care should be taken to protect it from impact or
abrasion when located in Zone 0. The polyurethane
paint finish may constitute an electrostatic hazard and
must only be cleaned with a damp cloth.
3. When the equipment is installed, particular
precautions must be taken to ensure, taking into
account the effect of process fluid temperature, that
the ambient temperature of the electrical housing of
the equipment meets the marked protection type
temperature range.
Flameproof certification
ABNT NBR IEC 60079-0: 2013
ABNT NBR IEC 60079-1: 2009 and 2011 correction
ABNT NBR IEC 60079-11: 2009
ABNT NBR IEC 60079-26: 2008 and 2009 correction
E2 Certification Number: NCC 11.0622 X
Ex d [ia] IIC T6 Ga/Gb (Integral Transmitter)
Ex d [ia Ga] IIC T6 Gb (Remote Transmitter)
Ex ia IIC T6 Ga (Remote Sensor)
Ambient temperature range: -50 °C ≤ Ta ≤ +70 °C
Process temperature range: -202 °C to +427 °C
Power Supply: 42 Vdc Max 4-20 mA HART
Power Supply: 32 Vdc Max Fieldbus
Transmitter Um = 250 V
Remote mounted sensor
In type of protection Ex ia IIC, only to be connected to the
associated Rosemount 8800D Vortex Flowmeter
electronics. The maximum length of the interconnecting
cable is 152 m (500 ft).
Special conditions for safe use (X):
1. For information regarding the dimensions of the
flameproof joints, the manufacturer shall be
contacted.
2. The Flowmeter is provided with special fasteners of
property class A2-70 of A4-70.
3. Units marked with “Warning: Electrostatic Charging
Hazard” may use non-conductive paint thicker than
0.2 mm. Precautions shall be taken to avoid ignition
due to electrostatic charge of the enclosure.
Combined Brazilian certifications (INMETRO)
K2 E2 and I2 Combination
B.5.6 EAC—Compliance with the
requirements of technical regulations
of the Customs Union
TR CU 020/2011—Electromagnetic compatibility of
technical means
TR CU 032/2013—On the safety of equipment operating
under excessive pressure
TR CU 012/2011—About the safety of equipment for use in
potentially explosive atmospheres
GOST R IEC 60079-0-2011, GOST R IEC 60079-1, GOST R IEC
60079-11-2010, GOST R IEC 60079-15-2010, GOST
31610.26-2002/IEC 60079-26:2002
E8 Type of protection flameproof enclosure «d» with
intrinsically safe flow sensor
Ex marking of the integral installation:
Ga/Gb Ex d [ia] IIC T6 X (-50°C ≤ Ta ≤ 70°C)
Ex marking of the remote installation:
Electronics module:
1Ex d [ia Ga] IIC T6 Gb X (-50°C ≤ Ta ≤ 70°C)
Flow sensor:
0Ex ia IIC T6 Ga X (-50°C ≤ Ta ≤ 70°C)
Electrical parameters:
Maximum DC supply voltage (with output signal 4-20
mA HART/pulse) 42 V;
Maximum DC supply voltage (with output signal
Foundation Fieldbus and FISCO) 32 V
Special conditions for safe use (X):
1. For flowmeters with Ex marking 0Ex ia IIC T6 Ga X, Ga /
Gb Ex d [ia] IIC T6 X and transmitter with Ex marking
1Ex d [ia Ga] IIC T6 Gb X
cabling in explosive area must be
conducted according to requirements of IEC
60079-14-2011. Sheath cables must be designed for
a maximum ambient temperature;
2. Remote installation should be made only with special
coaxial cable provided by the manufacturer of
flowmeters;