34
Reference Manual
00809-0100-4772, Rev FA
Installation
March 2016
Installation
Meter body should be insulated to achieve stated temperature accuracy. Insulation should
extend to the end of the bolt on the bottom of the meter body and should leave at least
1-in. (25 mm) of clearance around the electronics bracket. The electronics bracket and
electronics housing should not be insulated.
Figure 3-14. Flange Bolt Torquing Sequence
3.5.7 Remote electronics
If you order one of the remote electronics options (options R10, R20, R30, or RXX), the
flowmeter assembly will be shipped in two parts:
1. The meter body with an adapter installed in the support tube and an
interconnecting coaxial cable attached to it.
2. The electronics housing installed on a mounting bracket.
If you order the armored remote electronics options, follow the same instructions as for the
standard remote cable connection with the exception that the cable may not need to be run
through conduit. Armored includes the glands.
Do not loosen or remove the temperature connection at the electronics when the
housing integrity needs to be maintained.