78
Reference Manual
00809-0100-4772, Rev FA
Analog Input Function Block
March 2016
Analog Input Function Block
STATUS_OPTS 14 Propagate fault
forward
Uncertain if
Limited Bad if
Limited
Uncertain if
Man Mode
0 Read and Write
STDDEV 39 0 – 100 Percent 0 Read and Write The average absolute error
between the PV and its
previous mean value over that
evaluation time defined by
VAR_SCAN.
STRATEGY 03 0 – 65535 None 0 Read and Write The strategy field can be used
to identify grouping of blocks.
This data is not checked or
processed by the block.
TAG_DESC 02 32 text
characters
None none Read and Write The user description of the
intended application of the
block.
UPDATE_EVT 20 Not applicable None Not
applicable
Read only This alert is generated by any
change to the static data.
XD_SCALE 10 Any sensor
range
Refer to
Table 6-3.
When the engineering units of
the XD_SCALE are selected,
this will cause the engineering
units of the
PRIMARY_VALUE_RANGE in
the transducer block to change
to the same units.
1. MTA models only
2. Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale.
Table 6-2. Analog Input Function Block System Parameters
Parameter
Index
No.
Available
values
Units Default Read/Write Description